CHEMDIE- 1000

4-component, self-leveling, high gloss, high strength, high breakdown voltage dielectric flooring.

Product Description

4-component, self-leveling, high gloss, high strength, high breakdown voltage dielectric flooring.

Product Contents

ComponentDescription
1) ResinHazy, Liquid
2) HardenerTransparent, Liquid
3) Manufactured AggregatesWhitish, Powder
4) Pigment Colour ConcentrateRAL Colour Paste

For available RAL colours, refer current Chemsol Flooring and Topping shade card. Some colour variations may occur due to backfilling with sand in the case of bright colours. Under direct sunligh,t there may be some discolouration and colour variation over time.

Applications

Chemdie 1000 is specially formulated for applications where we required

  • Protection against electrical leakages & the resultant human risk in high voltage sub- stations.
  • Dust prevention ,
  • Chemical Resistance and
  • Aesthetic appeal.

It Finds uses in following Industries:

  • Use in high voltage sub- stations – switchgear panels, VCB’s, battery rooms,
  • Health Care
  • Clean room
  • Aerospace industries including airport hangars,

Product Data

Appearance / colour:Chemdeck TF[R] Resin:White viscous liquid
 Chemdeck TF [H] Hardener:Brown liquid
 pigment

Coloure paste

(supplied separately not part of kit)

Salient Features

  • Excellent self-leveling properties
  • High dielectric strength & insulation resistance.
  • Superior to conventional rubber mats.
  • Meets requirements of Class B (at 1.8 mm DFT) as per IS 15652: 2006 (>45KV BDV)
  • Pleasing Aesthetic Appeal due to Glossy, colourful Finish
  • Superior Adhesion to Concrete
  • Outstanding Mechanical Strength and Abrasion Resistance
  • Easy installation, cleaning & repair
  • Provides a clean dust dust-free atmosphere in panel rooms

Chemical Resistance

Excellent resistance is observed against distilled water, detergent solutions, alkalis and acids.

Mechanical/Physical properties

PropertyTest MethodValue and Unit
Mixing RatioNAPre-weighed kit to cover 10-12 sq m area @ 1000 micron thickness
FinishCPI* 1001Smooth, Glossy
Pot Life @ 30°CCPI 100230-35 minutes
Surface DryCPI 10023 Hours
Hard Dry [Open for foot traffic]CPI 100224 Hours
Full Cure [Vehicular Movement]CPI 100272 Hours
Compressive StrengthASTM C 579>600 Kg/cm²
Flexural StrengthASTM C 580>400 Kg/cm²
Tensile StrengthASTM C 307>200 Kg/cm²
Pull off Adhesion TestASTM D 4541Concrete Failure
Abrasion Resistance [Taber]ADTM D 406050 mg loss
Shore HardnessASTM D 2240D 80
BDV (1 coat of Chemprime + 2 coats of Chemdie 1000 top coat)IS 15652:200653 KV in air
AC Proof Voltage (1 coat of Chemprime + 2 coats of Chemdie 1000 top coat)IS 15652:2006>22 KV in air
Service TemperatureCPI 11220-50°C
Shelf LifeCPI 112212 months in original unopened container when stored between 10-30°C

 

Method of Application

All Chemsol Products are recommended to be applied only by Approved Applicators and should be handled after using proper PPE’s like Gloves, mask, goggles etc.

Application conditions

Substrate temperature: 10-40°C

Substrate moisture content: - <5%

Relative humidity: 8o%max

Note: The substrate temperature must be at least 30C above the prevalent dew point temperature to reduce chances of condensation on the floor.

Substrate Quality

The concrete substrate must be sound and of sufficient compressive strength (minimum 200 Kg/cm2) with a minimum pull-off strength of 15 Kg/cm2. The substrate must be clean, dry, and free of all contaminants such as dirt, oil, grease, coatings, and surface treatments, etc. If required, apply a test area first.

Substrate Preparation

Concrete substrates must be prepared mechanically using abrasive blast cleaning, Scarifying or grinding equipment to remove cement laitance and achieve an open textured surface. Remove weak concrete and expose surface defects such as blowholes and voids. Repairs to the substrate, filling of blowholes/voids, and surface levelling must be carried out using appropriate products. Ensure that the dust, loose and friable material is completely removed from all surfaces by brush and vacuum before application of the product. The concrete substrate has to be primed or levelled with Chemprime in order to achieve an even surface. Allow the primer to cure for 5-6 hours. After this, apply a top coat of CHEMDIE 1000

Mixing

Stir the resin part mechanically. Add colour paste into resin and mix till a uniform colour is achieved. Add hardener to this mixture and stir continuously for 2 minutes until a homogeneous mass is obtained. Add aggregates to this mixture and continue stirring for a further 3 minutes with a motorised helical paint stirrer until a uniform mix has been obtained. Overmixing must be avoided to minimise air entrainment. Note that the mixture has a stipulated pot life, hence the laying should immediately commence after mixing the contents. Allow it to dry for 12 hr., and again apply a 2nd coat of Chemdie 1000 on the applied cured material.

Curing Schedule

The epoxy curing reaction rate is temperature dependent. Refer to the following table to know how quickly the floor can be brought to service
Temp. (°C)Foot trafficFull cure
10°C48 hours120 hours
20°C 36 hours96 hours
30°C24 hours72 hours

Cleaning of Tools

Clean all tools and application equipment with thinner EP140 immediately after use. Hardened and/or cured material can only be removed mechanically.

Packing

Chemdie 1000 Resin, Hardener, and aggregates are available ina 16.4 kg pre-weighed kit.

Storage conditions

Store in dry and covered shed between 5 °C to 30 °C, away from sources of heat and naked flame.

Handling & Safety

Keep the containers tightly sealed when not in use. Avoid skin contact and inhalation of fumes (if any). While spraying it is advised to wear a mask. If it comes in contact with the body, wash affected parts with plenty of water. In case of persistent irritation, contact a physician.

*Disclaimer: The Information provided is based on our experience, thorough investigations & sophisticated testing methods, but due to the vast number of applications and usage methods, Chemsol Polymer Industries cannot accept responsibility of any kind for any particular result. It is the responsibility of the user to verify the suitability of the product for their end use and in accordance with the rules and regulations of that country /territory. All information provided pertaining to our products should be treated only as a guidance tool without any guarantee or warranty of any sorts.

* All CPI test methods are our scientifically designed internal test methods which can be shared upon request.